UL認(rèn)證Hawke防爆格蘭(Hawke 711 Cable Gland/Connector)
Hawke防爆格蘭(Hawke 711 Cable Gland/Connector)
上海頤品自動(dòng)化,:
上海頤品自動(dòng)化,:
Hawke 711 Cable Gland/Connector(American Series)
Explosion Proof / IECEx and ATEX Approved Flameproof Exd / Increased Safety Exe and Restricted Breathing ExnR
Application
Outdoor or indoor use.
For use with continuous corrugated aluminum, Metal Clad (MCHL) cable.
Features
Provides 360° armour grounding which is fully inspectable.
Grounding device remains in contact with the cable when disassembled for inspection.
Provides a barrier seal between the individual insulated cores within the cable and prevents entry of the products of an explosion into the cable.
Assembly of the cable gland/connector compresses and distributes the compound evenly to create a barrier seal at the point of entry into the enclosure.
Provides an outer deluge seal to prevent moisture ingress to the cable armour and enclosure. Deluge seal is coloured red to indicate hazardous locations product.
Provides a cable retention and low smoke and fume, zero halogen seal onto the cables outer jacket.
Materials & Finishes
The 711 cable gland/connector is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum. Brass NPT entries are nickel plated as standard.
Technical Data
- UL Listing No:
E84940. - Suitable for use in:
Class 1, Division 1, Gas Groups A, B , C and D.
Class 1, Zone 2, Gas Groups IIA, IIB and IIC.
AExd IIC and AExe II Class 1, Zone 2. - Flameproof Exd IIC Gb, Increased Safety Exe IIC Gb, Dust Extb IIIC Db
II 2 GD
ExnR IIC Gc, Extc IIIC DcII 3 GD
- Certificate No's
Sira 06ATEX1295X, Sira 07ATEX4330X and IECEx Sir 06.0082X. - Suitable for use in:
Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC. - Construction and Test Standards:
UL 2225, IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7, IEC/EN 60079-15, IEC/EN60079-31. - Ingress Protection:
IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X. - Deluge Protection to:
DTS01 - Operating Temperature Range:
-50°C to +60°C (UL) and -60°C to +80°C (ATEX / IECEx) - Note: 711 cable glands are supplied dual ATEX/UL marked as standard.
- Assembly Instruction Sheet:
AI 317 (UL, Sizes A to F). - AI 338 (UL, Size H).
- AI 389 (ATEX / IECEx).
CABLE GLAND/CONNECTOR SELECTION TABLE | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Size Ref. | Entry Thread Size | Cable Acceptance Details | ‘G’ Compressed Length | Hexagon Dimensions | ||||||||
Inner Sheath/Cores | ‘B’ Outer Jacket | |||||||||||
NPT | Metric * | ‘D’ Max. Over Cores | ‘E’ Armour Sheath | Max. No. Of Cores | Across Flats | Across Corners | ||||||
Standard | Option | Min. | Max. | Min. | Max. | |||||||
A | ½" | ¾" | M20 | 0.43" | 0.41" | 0.64" | 10 | 0.49" | 0.81" | 2.44" | 1.18" | 1.28" |
B | ¾" | 1" | M25 | 0.64" | 0.49" | 0.93" | 21 | 0.66" | 1.02" | 2.68" | 1.42" | 1.56" |
C | 1" | 1¼" | M32 | 0.86" | 0.85" | 1.23" | 42 | 0.87" | 1.30" | 2.76" | 1.81" | 1.99" |
C2 | 1¼" | 1½" | M40 | 1.04" | 1.17" | 1.59" | 60 | 1.10" | 1.61" | 2.96" | 2.17" | 2.36" |
D | 2" | 1½" | M50 | 1.46" | 1.37" | 1.96" | 80 | 1.42" | 2.07" | 3.18" | 2.56" | 2.79" |
E | 2½" | 2" | M63 | 1.88" | 1.76" | 2.55" | 100 | 1.81" | 2.57" | 3.21" | 3.15" | 3.46" |
F | 3" | 2½" | M75 | 2.32" | 2.29" | 2.98" | 120 | 2.24" | 3.07" | 3.54" | 3.74" | 4.09" |
H † | 3½" | - | M90 | 2.79" | 2.93" | 3.47" | 120 | 3.07" | 3.52" | 4.33" | 4.18" | 4.84" |
All dimensions in inches (except*). A - F size metric entry threads are 1.5mm pitch as standard with 15mm length of thread. For H size cable glands, a 2mm pitch is supplied as standard with a 20mm length of thread (1.5mm pitch with 15mm length of thread can be supplied) please specify when ordering. † UL approved only. |
中國區(qū)分銷商:
上海頤品自動(dòng)化科技有限公司
Shanghai Epin Automation Co.,Ltd.
Website:www.epinautomation。。com