UL認證Hawke防爆格蘭(Hawke ICG 623 Cable Gland)
Hawke防爆格蘭(Hawke ICG 623 Cable Gland)
上海頤品自動化,:
上海頤品自動化,:
Hawke ICG 623 Cable Gland
Flameproof Exd / Increased Safety Exe / Dust Extb / Dual Certified ATEX - IECEx
Application
Outdoor or indoor use.
For use with non-armoured elastomer and plastic insulated cables.
For particular use with:-
a) Cable inner sheaths that are not effectively filled, compact and/or circular, have tape bedding or have hygroscopic fillers.
b) Cables that exhibit ‘cold flow’ characteristics.
c) Enclosures containing an ignition source in gas group IIC areas or containing an ignition source in a Zone 1 area.
Ordering Format [ Gland Type / Size / Thread / Material / Options ]
Example without options: ICG 623 / C / M32 / Brass
Example with alternative seal option: ICG 623 / C / 1¼" NPT / Brass / S
Features
Provides a barrier seal between the individual insulated cores within the cable and prevents entry of the products of an explosion into the cable.
Assembly of the cable gland compresses and distributes the compound evenly to effect a barrier seal at the point of entry into the enclosure.
The compound chamber may be separated from the cured compound to ensure that the chamber has been effectively filled. If required, external voids can be repaired.
Provides a cable retention seal onto the cables outer sheath.
Materials & Finishes
The ICG 623 cable gland is manufactured in Brass (standard), Nickel Plated Brass, 316 Stainless Steel or Aluminum. Brass NPT entries are nickel plated as standard
Technical Data
- Exd IIC Gb, Exe IIC Gb, Extb IIIC Db
- Certificate No's
Baseefa06ATEX0058X and IECEx BAS 06.0015X. - Suitable for use in:
Zone 1, Zone 2, Zone 21, Zone 22 and in Gas Groups IIA, IIB and IIC. - Construction and Test Standards:
IEC/EN 60079-0, IEC/EN 60079-1, IEC/EN 60079-7 and IEC/EN 6079-31. - Ingress Protection:
IP66, IP67 and IP 68 (30 metres for 7 days) to IEC/EN 60529 and NEMA 4X. - Deluge Protection to:
DTS01 - Operating Temperature Range:
-60°C to +80°C - Assembly Instruction Sheet:
AI 305.
CABLE GLAND SELECTION TABLE | ||||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Size Ref. | Entry Thread Size | Cable Acceptance Details | ‘G’ Compressed Length | Hexagon Dimensions | ||||||||||
Inner Sheath/ Cores | ‘B’ Outer Sheath | |||||||||||||
Metric | NPT * | ‘D’ Max. Over Cores | ‘E’ Max. Inner Sheath | NOTE 1 Max. No. Of Cores | NOTE 2 Max. No. Of Cores | Standard Seal | Alternative (S) Seal | Across Flats | Across Corners | |||||
Standard | Option | Min. | Max. | Min. | Max. | |||||||||
Os | M20 | ½" | - | 8.0 | 8.0 | 12 | 6 | 3.0 | 8.0 | - | - | 56.4 | 24.0 | 26.5 |
O | M20 | ½" | - | 8.9 | 10.0 | 12 | 6 | 7.5 | 11.9 | - | - | 56.4 | 24.0 | 26.5 |
A | M20 | ¾" | ½" | 11.0 | 12.5 | 15 | 10 | 11.0 | 14.3 | 8.5 | 13.4 | 55.8 | 30.0 | 32.5 |
B | M25 | 1" | ¾" | 16.2 | 18.4 | 30 | 21 | 13.0 | 20.2 | 9.5 | 15.4 | 58.8 | 36.0 | 39.5 |
C | M32 | 1¼" | 1" | 21.9 | 24.7 | 42 | 42 | 19.0 | 26.5 | 15.5 | 21.2 | 62.0 | 46.0 | 50.5 |
C2 | M40 | 1½" | 1¼" | 26.3 | 29.7 | 60 | 60 | 25.0 | 32.5 | 22.0 | 28.0 | 64.5 | 55.0 | 60.6 |
D | M50 | 2" | 1½" | 37.1 | 41.7 | 80 | 80 | 31.5 | 44.4 | 27.5 | 34.8 | 72.8 | 65.0 | 70.8 |
E | M63 | 2½" | 2" | 47.8 | 53.5 | 100 | 100 | 42.5 | 56.3 | 39.0 | 46.5 | 77.0 | 80.0 | 88.0 |
F | M75 | 3" | 2½" | 59.0 | 66.2/65.3 † | 120 | 120 | 54.5 | 68.2 | 48.5 | 58.3 | 80.7 | 95.0 | 104.0 |
All dimensions in millimetres (except * where dimensions are in inches). Metric entry threads are 1.5mm pitch as standard. † Smaller value is applicable when selecting reduced NPT entry option. Note 1: ATEX/IECEx certification. Note 2: All other certification. |
中國區(qū)分銷商:
上海頤品自動化科技有限公司
Shanghai Epin Automation Co.,Ltd.
Website:www.epinautomation。。com
:sales@epinautomation.com
*: