Hawke PL520 Enclosure,Hawke防爆接線盒
Hawke PL520 Enclosure,Hawke防爆接線盒
上海頤品自動(dòng)化,:
Hawke PL520 Enclosure
Increased Safety Exe / Dual Certified ATEX - IECEx
Materials & Finishes
Glass Reinforced Plastic. Natural Black Finish.
Technical Data
- Increased Safety
II 2 GD Exe IIC Gb, Extb IIIC Db
- PL513 Certificate No's
Baseefa14ATEX0268X and IECEx BAS 14.0123X. - ZPL513 Certificate No's
Baseefa14ATEX0248U and IECEx BAS 14.0120U. - Suitable for use in:
Zone 1, Zone 2, Zone 21 and Zone 22. - Construction and Test Standards:
IEC/EN 60079-0, IEC/EN 60079-7, IEC/EN 60079-31. - Ingress Protection:
IP66 to IEC/EN 60529. - Operating Temperature Range:
-25°C to +75°C Low impact risk. - Temperature class & ambient:
T6 40°C, optional T5 with ambients up to 65°C.
MAXIMUM QUANTITY OF ENTRIES PER FACE | |||
---|---|---|---|
Thread Size | M16 / M20/O | M20/A | M25 |
Top & Bottom Faces A & C Qty. | 9 | 5 | 3 |
Side Faces B & D Qty. | 5* | 3 | 2 |
Optional: Earth continuity plate. * No serrated washer. * Max. across corners = 27.5mm * No Shroud Permitted. |
TERMINAL CAPACITY DATA | ||||||||
---|---|---|---|---|---|---|---|---|
Terminal Type | Conductor Size (mm²) | Max. Volts | Max. Physical Terminal Content | Reduced Terminal Content At Max. Terminal Amps | ||||
Min. | Max. | Terminal Quantity | Amps | Terminal Quantity | Amps | |||
WDU 2.5N | 0.5 | 2.5 | 420 | 32 | 8 | 8 | 17 | |
WDU 2.5 | 0.5 | 2.5 | 550 | 32 | 8 | 8 | 17 | |
WDU 4 | 0.5 | 4 | 690 | 26 | 11 | 7 | 22 | |
WDU 6 | 0.5 | 6 | 550 | 20 | 15 | 5 | 29 | |
WDU 10 | 1.5 | 10 | 550 | 16 | 22 | 4 | 40 | |
An earth terminal equal to that of the largest power terminal will be fitted. The terminals listed are restricted to a minimum operating temperature of -50°C. Max. number of terminals may reduce number of holes allowed. |
Enclosures Dissipated Wattage
ENCLOSURE DISSIPATED WATTAGE | |||||
---|---|---|---|---|---|
Enclosure Type | Temperature Class | ||||
T6 40°C & T5 55°C | T6 55°C | T5 40°C | T6 65°C | T5 65°C | |
PL511 | 1.6 | 1.0 | 2.2 | 0.6 | 1.2 |
PL513 GRP | 4.1 | 2.5 | 5.6 | 1.5 | 3.5 |
PL520 GRP | 4.8 | 3 | 6.6 | 1.8 | 3.6 |
PL612 GRP | 4.1 | 2.5 | 5.6 | 1.5 | 3 |
PL615 GRP | 6.4 | 4 | 8.8 | 2.4 | 4.8 |
PL620 GRP | 11.4 | 7.1 | 15.6 | 4.2 | 8.5 |
PL626 GRP | 11.4 | 7.1 | 15.6 | 4.2 | 8.5 |
PL630 GRP | 20.8 | 13 | 28.6 | 7.8 | 15.6 |
PL642 GRP | 20.8 | 13 | 28.6 | 7.8 | 15.6 |
PL644 GRP | 20.8 | 13 | 28.6 | 7.8 | 15.6 |
PL712 GRP | 3.35 | 2.14 | 4.6 | 1.2 | 2.4 |
PL722 GRP | 5.31 | 3.32 | 7.3 | 1.9 | 3.9 |
Size 1 Stainless Steel | 13.95 | 8.7 | 19.1 | 5.2 | 10.4 |
Size 2 Stainless Steel | 18.15 | 11.3 | 24.9 | 6.8 | 13.6 |
Size 2L Stainless Steel | 18.15 | 11.3 | 24.9 | 6.8 | 13.6 |
Size 3 Stainless Steel | 23.7 | 14.8 | 32.5 | 8.8 | 17.7 |
Size 4 Stainless Steel | 29.95 | 18.7 | 41.1 | 11.2 | 22.4 |
Size 4L Stainless Steel | 29.95 | 18.7 | 41.1 | 11.2 | 22.4 |
Size 5 Stainless Steel | 32.85 | 20.5 | 45.1 | 12.3 | 24.6 |
Size 6 Stainless Steel | 40 | 25 | 55 | 15 | 30 |
Size 7 Stainless Steel | 52 | 23.5 | 71.5 | 19.5 | 39 |
Size 8 Stainless Steel | 65 | 40.6 | 89.3 | 24.3 | 48.7 |
Size 9 Stainless Steel | 79.35 | 49.5 | 109.1 | 29.7 | 59.5 |
EJB1 | 4.74 | 2.96 | 6.51 | 1.778 | 3.55 |
EJB2 | 6.64 | 4.15 | 9.13 | 2.49 | 4.98 |
Dissipated Wattage Factor
The Dissipated Wattage Factor of the enclosures has been established by test to ensure that the maximum temperature as permitted by temperature certification is not exceeded. When terminal quantities greater than those at maximum amps are required (up to maximum physical quantity only) then the current shall be reduced accordingly to remain within the Dissipated Wattage Factor of the enclosure.
Combined Terminal Resistance Factor
This factor is used to determine the number of terminals that can be accommodated within the enclosure without exceeding the Wattage Factor. The Combined Terminal Resistance Factor is the sum of the individual terminal resistance's and the resistance of the cable core equal in length to the enclosure maximum diagonal. (Core Resistance is taken from BS6360). Combined terminal resistance factor.
Wattage to be Dissipated = N x F x I²
N = Number of Terminals. F = Combined Terminal Resistance Factor. I = Maximum Current.
e.g. Number of terminals in a PL630 Enclosure at 20.8 Watts - 10 x 'WDU 2.5' (1=17A), 2 x 'WDU 6' (1=29A), (10 x 0.003035 x 17 ² = 8.77 watts) + (2 x 0.001404 x 29 ²) = 2.36 watts). Total Watts = 8.77 + 2.36 = 11.13 watts.
Therefore this terminal combination is acceptable as the wattage is less than that of the PL630 maximum watts of 20.8 watts.
Note - If a smaller than maximum permitted conductor is fitted into a power terminal, then the smaller conductor resistance must be used when calculating the combined terminal resistance.
Transposed Formula
Combined Terminal Resistance
PL Series GRP Enclosures
Combined Terminal Resistance (Ω) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Terminal Type | Enclosure Type | |||||||||||
PL511 | PL513 | PL520 | PL612 | PL615 | PL620 | PL626 | PL630 | PL642 | PL644 | PL712 | PL722 | |
WDU 2.5N | 0.001490 | 0.001686 | 0.002057 | 0.001301 | 0.001657 | 0.002138 | 0.002398 | 0.003065 | 0.003561 | 0.004272 | 0.001412 | 0.002035 |
WDU 2.5 | 0.001460 | 0.001656 | 0.002689 | 0.001271 | 0.001627 | 0.002108 | 0.002368 | 0.003035 | 0.003531 | 0.004242 | 0.001382 | 0.002005 |
WDU 4 | 0.001013 | 0.001135 | 0.001366 | 0.000895 | 0.001117 | 0.001416 | 0.001578 | 0.001993 | 0.002302 | 0.002744 | 0.000965 | 0.001352 |
WDU 6 | 0.000749 | 0.000832 | 0.000985 | 0.000671 | 0.000819 | 0.001019 | 0.001127 | 0.001404 | 0.001611 | 0.001906 | 0.000717 | 0.000976 |
WDU 10 | - | 0.000528 | 0.000619 | 0.000432 | 0.000520 | 0.000639 | 0.000703 | 0.000868 | 0.000991 | 0.001166 | 0.000460 | 0.000614 |
WDU 16 | - | 0.000356 | 0.000413 | - | 0.000351 | 0.000426 | 0.000466 | 0.000570 | 0.000647 | 0.000757 | - | - |
WDU 35 | - | 0.000194 | 0.000220 | - | - | 0.000226 | 0.000244 | 0.000291 | 0.000326 | 0.000377 | - | - |
WDU 50N | - | - | - | - | - | 0.000164 | - | 0.0002113 | - | 0.000202 | - | - |
WDU 70N | - | - | - | - | - | 0.000124 | - | 0.000158 | 0.000176 | - | - | - |
UT 2.5 | 0.001113 | - | - | - | - | - | - | - | - | - | - | - |
UT 4 | 0.000729 | - | - | - | - | - | - | - | - | - | - | - |
UT 6 | 0.000479 | - | - | - | - | - | - | - | - | - | - | - |
PL Series Enclosures Maximum Physical Quantity Of Terminals
W Series And Direct Mounted Terminals
MAXIMUM PHYSICAL QUANTITY OF TERMINALS | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Terminal Type | Enclosure Type | ||||||||||||
PL511 | PL513 | PL520 | PL612 | PL615 | PL620 | PL626 | PL630 | PL642 | PL644 | PL712 | PL722 | ||
1 Diagonal Rail | 2 Vertical Rails | ||||||||||||
WDU 2.5N | 10 | 18 | 30 | 12 + 1 Earth (1 central or offset entry only) | N/A | N/A | 38 + 1 Earth | N/A | N/A | 115 | 164 | 12 + 1 Earth (1 central entry only) | N/A |
WDU 2.5 | 9 | 18 | 30 | 10 + 1 Earth (1 offset entry only) | 14 + 1 Earth | 24 + 1 Earth | 38 + 1 Earth | 50 + 1 Earth | 76 + 2 Earths (38 + 1 earth per rail) | 115 | 164 | 10 + 1 Earth (1 central entry only) | 35 + 1 Earth (No entries on faces B & D) |
WDU 4 | 8 | 15 | 25 | 8 + 1 Earth (1 offset entry only) | 12 + 1 Earth | 20 + 1 Earth | 32 + 1 Earth | 42 + 1 Earth | 64 + 2 Earths (32 + 1 earth per rail) | 97 | 137 | 8 + 1 Earth (1 central entry only) | 29 + 1 Earth (No entries on faces B & D) |
WDU 6 | 6 | 11 | 20 | 7 + 1 Earth (1 offset entry only) | 9 + 1 Earth | 15 + 1 Earth | 24 + 1 Earth | 30 + 1 Earth | 48 + 2 Earths (24 + 1 earth per rail) | 73 | 104 | 7 + 1 Earth (1 central entry only) | 22 + 1 Earth (No entries on faces B & D) |
WDU 10 | N/A | 9 | 15 | 5 + 1 Earth (1 offset entry only) | 7 + 1 Earth | 12 + 1 Earth | 19 + 1 Earth | 25 + 1 Earth | 36 + 2 Earths (18 + 1 earth per rail) | 59 | 83 | 5 + 1 Earth (1central entry only) | 17 + 1 Earth (No entries on faces B & D) |
WDU 16 | N/A | 7 | 12 | N/A | 6 + 1 Earth (1 offset entry only) | 9 + 1 Earth | 16 + 1 Earth | 20 + 1 Earth | 30 + 2 Earths (15 + 1 earth per rail) | 49 | 68 | N/A | N/A |
WDU 35 | N/A | N/A | 9 | N/A | N/A | 6 + 1 Earth | 12 + 1 Earth | 15 + 1 Earth | 22 + 2 Earths (11 + 1 earth per rail) | 17 | 50 | N/A | N/A |
WDU50N | N/A | N/A | N/A | N/A | N/A | 5 + 1 Earth | N/A | 11 + 1 Earth | N/A | N/A | N/A | N/A | N/A |
WDU 70N | N/A | N/A | N/A | N/A | N/A | 4 + 1 Earth | N/A | 11 + 1 Earth (Conductor termination difficult - Advise 9 + 1 Earth) | N/A | 15 | 15 | N/A | N/A |
UT 2.5 | 9 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
UT 4 | 8 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
UT 6 | 6 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
BK6 | N/A | N/A | N/A | 1 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | 1 | N/A |
MK6/6 | N/A | N/A | N/A | 1 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | 1 | N/A |
HTB/6 | N/A | N/A | N/A | 1 | 1 | 2 | N/A | N/A | N/A | N/A | N/A | 1 | N/A |
Notes:
Earths (PL511, PL513, PL520, PL612 and PL712) The rail earths may be replaced by a pillar earth, but a bracket shall be fitted at the end of the terminal stack in it's place.
Entries (PL511, PL513, PL520, PL612, PL615 ,PL626, PL712 and PL722) Where the quantity of entries has been restricted, this is due to limited space. If multiple entries are required, then the quantity of power terminals shall be reduced accordingly. PL712 - It may be possible for some maximum terminal assemblies to use two M20/O entry positions.
Rails (PL513, PL520, PL612, PL615, PL620 and PL712) 1 Diagonal rail.
PL511, PL626 and PL722: 1 Horizontal rail.
PL630: 1 diagonal or 2 vertical rails.
中國(guó)區(qū)分銷商:
上海頤品自動(dòng)化科技有限公司
Shanghai Epin Automation Co.,Ltd.
Website:www.epinautomation。。com
:sales@epinautomation.com
*: