PrimeTest 250
The handheld PrimeTest 250 PAT tester features all of the portable appliance testing electrical safety tests required to meet the IEE Code of Practice including RCD trip time, protective conductor current and touch current.
This portable appliance tester also includes a 250V DC insulation test suitable for testing sensitive electrical appliances and surge protected leads, and can test 3 phase industrial plant and equipment*. Connecting this battery-powered tester to a mains supply allows protective conductor current or touch current measurements to be made automatically.
Using the PrimeTest 250 ensures your portable appliance testing is now quicker and easier because all electrical safety tests are carried out against pre-set limits with measured test result values and clear PASS/FAIL indication on the large display.
Earth continuity
Output Current | 200mA |
Test Voltage (o/c) | 9V DC nominal |
Test Duration (Class I Test) | 2s nominal |
Display Range | 0.01ohm to 19.99ohm |
Pass Value (Class I Test) | 0.2ohm |
Insulation resistance
Test Voltage | 250/500VDC @1mA nominal, < 2mA (s/c) |
Test Duration (Class I or II) | 2s |
Display Range | 0.01Mohm to 19.99Mohm |
Pass Value | 1.0MOhm Class I |
| 2.0MOhm Class II |
Equivalent leakage
Test Voltage | 40V Nominal AC 50Hz Open Circuit |
Test Duration | 2s nominal |
Display Range | 0.1mA to 19.99mA |
Pass Value | 0.75mA CLI / 0.25mA CL II |
IEC lead test
Test voltage | 5V DC nominal |
Test Duration | Time for test (2s max) |
Test | Live/Neutral Checks for o/c, s/c and crossed |
Protective Conductor Current
Test Voltage | Supply Voltage, max current 13A |
Test Duration | 30s maximum |
Display Range | 0.15mA to 9.99mA |
Pass Value | 0.75mA/3.5mA (user selectable with 0.75mA as default) |
Touch current
Test Voltage | Supply Voltage, max current 13A |
Test Duration | 30s maximum |
Display Range | 0.10mA to 5.00mA |
Pass Value | 0.25mA |