As flame-retardant three or four conductor power cables rated 600 volts, 90 Deg. C. in wet or dry locations. Specifically approved for installation in cable trays per Article 336 of the NEC. Type TC cable is also approved for use in Class I and II, Division 2 hazardous locations. Cables may be installed in open air, in ducts or conduits, in tray or trough, or direct buried.
Construction
Class B stranded uncoated copper conductor, XLPE crosslinked polyethylene insulation, surface print phase identification. Three or four insulated conductors twisted with a Class B stranded uncoated copper grounding conductor and suitable fillers, cable tape, PVC jacket overall, surface printed.
Standards
1) Listed by UL as Type TC per Standard 1277 for Tray Cables.
2) Individual conductors UL listed as Type XHHW-2.
3) Overall jacket UL listed as Sunlight Resistant.
4) Cables pass UL and IEEE-383 ribbon burner flame tests.
5) Cables pass IEEE1202/CSA FT4 (70,000 BTU/hr) cable tray flame test (2 AWG and larger).
6) Cables UL listed for Direct Burial.
7) Cables UL listed for Open Wiring.
8) Cables meet requirements of ICEA S-9568/NEMA WC70.
Options
Consult us for a variety of alternate constructions for specific applications.