西門子6ES7174-0AA10-0AA0,西門子IM174接口模塊, 西門子IM174 PROFIBUS模塊,西門子174-0AA10-0AA0,西門子PLC代理商
SIMATIC S7-300,IM174接口模塊,用于連接模擬驅(qū)動(dòng)器和步進(jìn)驅(qū)動(dòng)器,通過ISOCHRONUS PROFIBUS到達(dá)運(yùn)動(dòng)控制器,有4條通道(4 ENCOD.INP., 4 模擬量輸出)可通過STEP7 V5.4 SP4組態(tài)
訂貨號(hào);6ES7174-0AA10-0AA0
上海翰粵自動(dòng)化系統(tǒng)有限公司
:張寬順(銷售工程師)
(24小時(shí)售后技術(shù)服務(wù))
商務(wù): 2880585023
():
傳真():
地址:上海市松江區(qū)思賢路2399弄185號(hào)
本公司優(yōu)勢(shì)產(chǎn)品:西門子6ES7-200/300/400/1200/6EP/
6AV/6GK/ET200/6SE變頻器/電纜/DP接頭/觸摸屏/變頻器/數(shù)控伺服備件
歡迎您高品質(zhì)西門子驅(qū)動(dòng)和自動(dòng)化產(chǎn)品價(jià)格
如需選型請(qǐng)準(zhǔn)備好您需要產(chǎn)品的詳細(xì)參數(shù)我們將竭誠(chéng)為您服務(wù)
使用 IM 174 PROFIBUS 模塊,可以通過同步 PROFIBUS DP 將zui多 4 個(gè)驅(qū)動(dòng)器連接到運(yùn)動(dòng)控制器??梢赃B接帶模擬量設(shè)定點(diǎn)接口或脈沖-方向接口的電氣或液壓驅(qū)動(dòng)器或步進(jìn)驅(qū)動(dòng)器。IM 174 是一個(gè) PROFIBUS DP 從站,可在同步 PROFIBUS DP 上運(yùn)行。
它可結(jié)合以下部件使用:
? SIMATIC CPU 41x-2 DP, CPU 31x-2 DP, CPU 31xT-2 DP, WinAC RTX 2008
? SIMOTION C2xx, SIMOTION P350, SIMOTION D4x5
西門子
具有以下接口和狀態(tài)顯示:
- 同步 PROFIBUS DP 的連接(zui大 12 Mbit/s)
- 4 個(gè)位置采集編碼器輸入,每個(gè)輸入可連接到 RS422 增量式編碼器或 SSI 值編碼器。
- 4 個(gè) ±10 V 模擬量輸出,用于連接帶有模擬量設(shè)定點(diǎn)接口的驅(qū)動(dòng)器
- 4 個(gè)用于控制步進(jìn)驅(qū)動(dòng)器(帶或不帶編碼器接口)的接口
- 10 點(diǎn)數(shù)字量輸入,24 V DC(例如,用于參考點(diǎn)接近、控制器就緒信號(hào))
- 8 點(diǎn)數(shù)字量輸出,24 VDC,0.5 A(例如,用于驅(qū)動(dòng)器使能)
- 2 個(gè)用于就緒信號(hào)的繼電器觸點(diǎn)
- 4 個(gè)用于軸 1 至 4 驅(qū)動(dòng)器使能的繼電器觸點(diǎn)
- 通過 4 個(gè)診斷 LED 進(jìn)行內(nèi)置狀態(tài)顯示
所有連接都在前面進(jìn)行。
需要使用一個(gè)外部電源 (24 VDC) 來為模塊和數(shù)字量輸出供電。
西門子
驅(qū)動(dòng)器的實(shí)際值(編碼器值)通過 PROFIBUS DP 從 IM 174 傳輸?shù)竭\(yùn)動(dòng)控制器。控制單元的位置控制器計(jì)算速度設(shè)定點(diǎn)。這個(gè)值通過 PROFIBUS DP 傳輸?shù)?IM 174,然后在輸出到驅(qū)動(dòng)器。
Technical Specifications
Order number | ||
---|---|---|
IM 174 FOR CONNECTING ANALOG DRIVES | ||
Product type designation | ||
Supply voltage | ||
Rated value (DC) | ||
| Yes | |
permissible range, lower limit (DC) | 20.4 V | |
permissible range, upper limit (DC) | 28.8 V | |
Input current | ||
Current consumption, max. | 500 mA | |
from backplane bus 5 V DC, max. | 100 mA | |
Encoder supply | ||
5 V encoder supply | ||
| Yes | |
| 1.2 A | |
| 25 m | |
24 V encoder supply | ||
| Yes | |
| 1.4 A | |
| 100 m | |
Absolute encoder (SSI) encoder supply | ||
| Yes | |
| Yes | |
Power losses | ||
Power loss, typ. | 12 W | |
Digital inputs | ||
Number of digital inputs | 10 | |
Input voltage | ||
| -3 to +5V | |
| +11 to +30V | |
Input current | ||
| 2 mA | |
| 8 mA | |
Input delay (for rated value of input voltage) | ||
for standard inputs | ||
| 15 μs | |
Cable length | ||
| 100 m | |
Digital outputs | ||
Number of digital outputs | 8 | |
short-circuit protection | Yes | |
Switching capacity of the outputs | ||
| 1 A | |
| 30 W | |
Output voltage | ||
| 24 V; L+ | |
| L+ (-3 V) | |
| 3 V | |
Output current | ||
| 5 mA | |
| 300 mA | |
| 0.4 mA | |
Output delay with resistive load | ||
| 500 μs | |
Switching frequency | ||
| 500 Hz | |
| 0.5 Hz | |
Relay outputs | ||
| 4 | |
| 50 000 | |
Switching capacity of contacts | ||
| 1 A | |
Cable length | ||
| 600 m | |
Analog outputs | ||
Number of analog outputs | 4 | |
Output ranges, voltage | ||
| Yes | |
Analog value creation | ||
Integration and conversion time/resolution per channel | ||
| 15 bit | |
Encoder | ||
Number of connectable encoders, max. | 4 | |
Connectable encoders | ||
| Yes | |
| Yes | |
| Yes | |
| 2 mA | |
Encoder signals, incremental encoder (symmetrical) | ||
| A, notA, B, notB | |
| N, notN | |
| 5 V difference signal (phys. RS 422) | |
| 1 MHz | |
| 35 m; 35 m at max. 500 kHz; 10 m at max. 1 MHz | |
Encoder signals, absolute encoder (SSI) | ||
| 5 V difference signal (phys. RS 422) | |
| DATA, notDATA | |
| CL, notCL | |
| 13, 21, 24 bit | |
| 1.5 MHz; 187.5 KHz 1.5 MHz (parameterizable) | |
| 1 | |
| 1 | |
| 250 m; 250 m at 187.5 kHz, 10 m at 1.5 MHz | |
Isochronous mode | ||
Isochronous operation (application synchronized up to terminal) | Yes | |
shortest clock pulse | 1.5 ms | |
Interrupts/diagnostics/status information | ||
Alarms | ||
| Yes | |
Drive interface | ||
Number of drive interfaces | 4 | |
Analog drive | ||
Setpoint signal | ||
| Yes; max. 45 mA, min. 3.3 kOhm load impedance | |
| -10.5 V to +10.5 V | |
| -3 to +3 mA | |
Output controller release | ||
| 4 | |
| 30 V | |
| 1 A | |
| 30 V·A | |
| 50 000; at 30 V DC, 1 A | |
| 35 m | |
Signal output I | ||
| 2 | |
| 30 V | |
| 1 A | |
| 30 V·A | |
| 50 000; at 30 V DC, 1 A | |
| 35 m | |
Signal output II | ||
| 2 V; R = 100 Ohm | |
| 3.7 V; 3.7 V at I = -20 mA; 4.5 V at I = -100 μA, | |
| 1 V; For I = -20 mA | |
| 55 ? | |
| 60 mA | |
Signal output III | ||
| 750 kHz | |
| 50 m; in hybrid operation with analog axes 35 m, in asymmetrical transmission 10 m | |
Galvanic isolation | ||
Galvanic isolation digital inputs | ||
| Yes; to encoders, analog outputs, DP interface; no to other DI/DOs | |
Galvanic isolation digital outputs | ||
| Yes; to encoders, analog outputs, DP interface; no to other DI/DOs | |
Connection method | ||
required front connector | 40-pin | |
Dimensions | ||
Width | 160 mm | |
Height | 125 mm | |
Depth | 118 mm | |
Weights | ||
Weight, approx. | 1 kg |