當前位置:上海頤品自動化科技有限公司>>*防爆格蘭等>>英國Hawke防爆格蘭等>> Hawke PL620 Enclosure,Hawke防爆接線盒
參 考 價 | 面議 |
產品型號
品 牌
廠商性質生產商
所 在 地上海
聯(lián)系方式:張凱文查看聯(lián)系方式
更新時間:2022-12-05 07:20:18瀏覽次數(shù):1305次
聯(lián)系我時,請告知來自 儀表網(wǎng)Hawke PL620 Enclosure,Hawke防爆接線盒
Hawke PL620 Enclosure,Hawke防爆接線盒
上海頤品自動化,:
Glass Reinforced Polyester. Natural Black Finish. Flame Retardant to IEC 92.1 Clause 2.38
MAXIMUM QUANTITY OF ENTRIES PER FACE | |||||
---|---|---|---|---|---|
Thread Size | M16/M20 | M25 | M32 | M40 | M50 |
Quantity | 6 | 4 | 2 | 1# | 1# |
# Not possible with an earth continuity plate. Optional: Earth continuity plate. |
TERMINAL CAPACITY DATA | ||||||||
---|---|---|---|---|---|---|---|---|
Terminal Type | Conductor Size (mm²) | Max. Volts | Max. Physical Terminal Content | Reduced Terminal Content At Max. Terminal Amps | ||||
Min. | Max. | Terminal Quantity | Amps | Terminal Quantity | Amps | |||
WDU 2.5 | 0.5 | 2.5 | 550 | 24 | 15 | 18 | 17 | |
WDU 4 | 0.5 | 4 | 690 | 20 | 20 | 16 | 22 | |
WDU 6 | 0.5 | 6 | 550 | 15 | 27 | 12 | 29 | |
WDU 10 | 1.5 | 10 | 550 | 12 | 38 | 10 | 40 | |
WDU 16 | 1.5 | 16 | 690 | 9 | 53 | 9 | 53 | |
WDU 35 | 2.5 | 35 | 690 | 6 | 87 | 6 | 87 | |
WDU 50N | 6 | 50 | 690 | 5 | 88 | 5 | 88 | |
WDU 70 | 10 | 70 | 690 | 4 | 134 | 4 | 134 | |
An earth terminal equal to that of the largest power terminal will be fitted. The terminals listed are restricted to a minimum operating temperature of -50°C. |
To ensure that the maximum temperature as permitted by certification is not exceeded, the dissipated wattage factor formula is used: W = N x F x I² (see enclosure wattage factor).
It is not permitted to fit more than one conductor per side in rail or direct mounted terminals unless using an insulated Bootlace Ferrule.
Linked and mixed terminal arrangements other than those specified in the data tables are available, but the voltage and current figures may be affected to ensure the maximum certified wattage factor is not exceeded. Please contact Hawke Technical Sales for more information.
When connecting a terminal with a conductor that is less than maximum size permitted for that terminal type, the maximum amps per pole must be reduced to suit i.e. an WDU10 (10mm²) terminal fitted with a 4mm² conductor will have the current rating reduced to that of the current rating permitted through the WDU4 (4mm²) terminal.
For Intrinsically Safe Applications, Exe power terminals can be supplied in blue on request. (Note: the enclosure will remain Exe certified).
An earth terminal must be fitted inside the enclosure. (Note: Power terminals may be used as ‘clean earths’).
The enclosure has tapped metric entry threads as standard. Tapered threads are not permitted in plastic enclosures due to risk of stress cracking.
The customer may drill and tap entry holes in the enclosure providing they are in accordance with the relevant code of practice and comply with the certification, contact Hawke Technical Sales for more information.
When mixed entries are required on a face, contact Hawke Technical Sales for more information.
Entries into the enclosure must be via a suitable, approved entry device.
All unused entry holes must be fitted with a stopping plug as listed on the enclosure certificate.
PL6 Series Certification: II 2 GD Exe IIC Gb, Extb IIIC, Db.
PL7 Series Certification: II 2 GD Exe IIC Gb, Extb IIIC, Db.
Zones of Use: Zone 1, Zone 2, Zone 21 & Zone 22.
Temperature Class & Ambients: T6 40°C as standard. Optional T5 with ambients up to 65°C.
Operating Temperature Range: -60°C to +75°C.
PL6 Series Degree of Protection: IP66, IP67 and Deluge proof to DTS01.
PL7 Series Degree of Protection: IP66 and Deluge proof to DTS01.
Material: Glass Reinforced Polyester. Flame Retardant to (IEC92.1 clause 2.38).
Finish: Natural Black.
PL6 Series Impact Resistance: Up to 7Nm.
PL7 Series Impact Resistance: Up to 7Nm.
Weatherproofing: By captive moulded clear silicone gasket.
Certification Label: Stainless Steel or optional certified self adhesive foil.
Lid Fixing Screws: Stainless Steel (complete with nylon retaining washer).
Additional Options: Breather/Drain devices. Internal/external earth stud. Epoxy paint finish for colour coding. EMI/RFI coating for EMC requirements.
Additional Labels: Stainless Steel or laminated plastic (traffolyte) for external use only or optional (certified) self adhesive foil for external and/or internal use.
These Enclosures may be fitted with an earth continuity plate in plated mild steel as standard or optional brass when requested by the customer. (Note: A locknut is required on Cable Glands and metal stopping plugs to ensure earth continuity through the plate).
ENCLOSURE DISSIPATED WATTAGE | |||||
---|---|---|---|---|---|
Enclosure Type | Temperature Class | ||||
T6 40°C & T5 55°C | T6 55°C | T5 40°C | T6 65°C | T5 65°C | |
PL511 | 1.6 | 1.0 | 2.2 | 0.6 | 1.2 |
PL513 GRP | 4.1 | 2.5 | 5.6 | 1.5 | 3.5 |
PL520 GRP | 4.8 | 3 | 6.6 | 1.8 | 3.6 |
PL612 GRP | 4.1 | 2.5 | 5.6 | 1.5 | 3 |
PL615 GRP | 6.4 | 4 | 8.8 | 2.4 | 4.8 |
PL620 GRP | 11.4 | 7.1 | 15.6 | 4.2 | 8.5 |
PL626 GRP | 11.4 | 7.1 | 15.6 | 4.2 | 8.5 |
PL630 GRP | 20.8 | 13 | 28.6 | 7.8 | 15.6 |
PL642 GRP | 20.8 | 13 | 28.6 | 7.8 | 15.6 |
PL644 GRP | 20.8 | 13 | 28.6 | 7.8 | 15.6 |
PL712 GRP | 3.35 | 2.14 | 4.6 | 1.2 | 2.4 |
PL722 GRP | 5.31 | 3.32 | 7.3 | 1.9 | 3.9 |
Size 1 Stainless Steel | 13.95 | 8.7 | 19.1 | 5.2 | 10.4 |
Size 2 Stainless Steel | 18.15 | 11.3 | 24.9 | 6.8 | 13.6 |
Size 2L Stainless Steel | 18.15 | 11.3 | 24.9 | 6.8 | 13.6 |
Size 3 Stainless Steel | 23.7 | 14.8 | 32.5 | 8.8 | 17.7 |
Size 4 Stainless Steel | 29.95 | 18.7 | 41.1 | 11.2 | 22.4 |
Size 4L Stainless Steel | 29.95 | 18.7 | 41.1 | 11.2 | 22.4 |
Size 5 Stainless Steel | 32.85 | 20.5 | 45.1 | 12.3 | 24.6 |
Size 6 Stainless Steel | 40 | 25 | 55 | 15 | 30 |
Size 7 Stainless Steel | 52 | 23.5 | 71.5 | 19.5 | 39 |
Size 8 Stainless Steel | 65 | 40.6 | 89.3 | 24.3 | 48.7 |
Size 9 Stainless Steel | 79.35 | 49.5 | 109.1 | 29.7 | 59.5 |
EJB1 | 4.74 | 2.96 | 6.51 | 1.778 | 3.55 |
EJB2 | 6.64 | 4.15 | 9.13 | 2.49 | 4.98 |
Dissipated Wattage Factor
The Dissipated Wattage Factor of the enclosures has been established by test to ensure that the maximum temperature as permitted by temperature certification is not exceeded. When terminal quantities greater than those at maximum amps are required (up to maximum physical quantity only) then the current shall be reduced accordingly to remain within the Dissipated Wattage Factor of the enclosure.
Combined Terminal Resistance Factor
This factor is used to determine the number of terminals that can be accommodated within the enclosure without exceeding the Wattage Factor. The Combined Terminal Resistance Factor is the sum of the individual terminal resistance's and the resistance of the cable core equal in length to the enclosure maximum diagonal. (Core Resistance is taken from BS6360). Combined terminal resistance factor.
Wattage to be Dissipated = N x F x I²
N = Number of Terminals. F = Combined Terminal Resistance Factor. I = Maximum Current.
e.g. Number of terminals in a PL630 Enclosure at 20.8 Watts - 10 x 'WDU 2.5' (1=17A), 2 x 'WDU 6' (1=29A), (10 x 0.003035 x 17 ² = 8.77 watts) + (2 x 0.001404 x 29 ²) = 2.36 watts). Total Watts = 8.77 + 2.36 = 11.13 watts.
Therefore this terminal combination is acceptable as the wattage is less than that of the PL630 maximum watts of 20.8 watts.
Note - If a smaller than maximum permitted conductor is fitted into a power terminal, then the smaller conductor resistance must be used when calculating the combined terminal resistance.
Transposed Formula
PL Series GRP Enclosures
Combined Terminal Resistance (Ω) | ||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|
Terminal Type | Enclosure Type | |||||||||||
PL511 | PL513 | PL520 | PL612 | PL615 | PL620 | PL626 | PL630 | PL642 | PL644 | PL712 | PL722 | |
WDU 2.5N | 0.001490 | 0.001686 | 0.002057 | 0.001301 | 0.001657 | 0.002138 | 0.002398 | 0.003065 | 0.003561 | 0.004272 | 0.001412 | 0.002035 |
WDU 2.5 | 0.001460 | 0.001656 | 0.002689 | 0.001271 | 0.001627 | 0.002108 | 0.002368 | 0.003035 | 0.003531 | 0.004242 | 0.001382 | 0.002005 |
WDU 4 | 0.001013 | 0.001135 | 0.001366 | 0.000895 | 0.001117 | 0.001416 | 0.001578 | 0.001993 | 0.002302 | 0.002744 | 0.000965 | 0.001352 |
WDU 6 | 0.000749 | 0.000832 | 0.000985 | 0.000671 | 0.000819 | 0.001019 | 0.001127 | 0.001404 | 0.001611 | 0.001906 | 0.000717 | 0.000976 |
WDU 10 | - | 0.000528 | 0.000619 | 0.000432 | 0.000520 | 0.000639 | 0.000703 | 0.000868 | 0.000991 | 0.001166 | 0.000460 | 0.000614 |
WDU 16 | - | 0.000356 | 0.000413 | - | 0.000351 | 0.000426 | 0.000466 | 0.000570 | 0.000647 | 0.000757 | - | - |
WDU 35 | - | 0.000194 | 0.000220 | - | - | 0.000226 | 0.000244 | 0.000291 | 0.000326 | 0.000377 | - | - |
WDU 50N | - | - | - | - | - | 0.000164 | - | 0.0002113 | - | 0.000202 | - | - |
WDU 70N | - | - | - | - | - | 0.000124 | - | 0.000158 | 0.000176 | - | - | - |
UT 2.5 | 0.001113 | - | - | - | - | - | - | - | - | - | - | - |
UT 4 | 0.000729 | - | - | - | - | - | - | - | - | - | - | - |
UT 6 | 0.000479 | - | - | - | - | - | - | - | - | - | - | - |
W Series And Direct Mounted Terminals
MAXIMUM PHYSICAL QUANTITY OF TERMINALS | |||||||||||||
---|---|---|---|---|---|---|---|---|---|---|---|---|---|
Terminal Type | Enclosure Type | ||||||||||||
PL511 | PL513 | PL520 | PL612 | PL615 | PL620 | PL626 | PL630 | PL642 | PL644 | PL712 | PL722 | ||
1 Diagonal Rail | 2 Vertical Rails | ||||||||||||
WDU 2.5N | 10 | 18 | 30 | 12 + 1 Earth (1 central or offset entry only) | N/A | N/A | 38 + 1 Earth | N/A | N/A | 115 | 164 | 12 + 1 Earth (1 central entry only) | N/A |
WDU 2.5 | 9 | 18 | 30 | 10 + 1 Earth (1 offset entry only) | 14 + 1 Earth | 24 + 1 Earth | 38 + 1 Earth | 50 + 1 Earth | 76 + 2 Earths (38 + 1 earth per rail) | 115 | 164 | 10 + 1 Earth (1 central entry only) | 35 + 1 Earth (No entries on faces B & D) |
WDU 4 | 8 | 15 | 25 | 8 + 1 Earth (1 offset entry only) | 12 + 1 Earth | 20 + 1 Earth | 32 + 1 Earth | 42 + 1 Earth | 64 + 2 Earths (32 + 1 earth per rail) | 97 | 137 | 8 + 1 Earth (1 central entry only) | 29 + 1 Earth (No entries on faces B & D) |
WDU 6 | 6 | 11 | 20 | 7 + 1 Earth (1 offset entry only) | 9 + 1 Earth | 15 + 1 Earth | 24 + 1 Earth | 30 + 1 Earth | 48 + 2 Earths (24 + 1 earth per rail) | 73 | 104 | 7 + 1 Earth (1 central entry only) | 22 + 1 Earth (No entries on faces B & D) |
WDU 10 | N/A | 9 | 15 | 5 + 1 Earth (1 offset entry only) | 7 + 1 Earth | 12 + 1 Earth | 19 + 1 Earth | 25 + 1 Earth | 36 + 2 Earths (18 + 1 earth per rail) | 59 | 83 | 5 + 1 Earth (1central entry only) | 17 + 1 Earth (No entries on faces B & D) |
WDU 16 | N/A | 7 | 12 | N/A | 6 + 1 Earth (1 offset entry only) | 9 + 1 Earth | 16 + 1 Earth | 20 + 1 Earth | 30 + 2 Earths (15 + 1 earth per rail) | 49 | 68 | N/A | N/A |
WDU 35 | N/A | N/A | 9 | N/A | N/A | 6 + 1 Earth | 12 + 1 Earth | 15 + 1 Earth | 22 + 2 Earths (11 + 1 earth per rail) | 17 | 50 | N/A | N/A |
WDU50N | N/A | N/A | N/A | N/A | N/A | 5 + 1 Earth | N/A | 11 + 1 Earth | N/A | N/A | N/A | N/A | N/A |
WDU 70N | N/A | N/A | N/A | N/A | N/A | 4 + 1 Earth | N/A | 11 + 1 Earth (Conductor termination difficult - Advise 9 + 1 Earth) | N/A | 15 | 15 | N/A | N/A |
UT 2.5 | 9 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
UT 4 | 8 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
UT 6 | 6 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A | N/A |
BK6 | N/A | N/A | N/A | 1 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | 1 | N/A |
MK6/6 | N/A | N/A | N/A | 1 | N/A | N/A | N/A | N/A | N/A | N/A | N/A | 1 | N/A |
HTB/6 | N/A | N/A | N/A | 1 | 1 | 2 | N/A | N/A | N/A | N/A | N/A | 1 | N/A |
Notes:
Earths (PL511, PL513, PL520, PL612 and PL712) The rail earths may be replaced by a pillar earth, but a bracket shall be fitted at the end of the terminal stack in it's place.
Entries (PL511, PL513, PL520, PL612, PL615 ,PL626, PL712 and PL722) Where the quantity of entries has been restricted, this is due to limited space. If multiple entries are required, then the quantity of power terminals shall be reduced accordingly. PL712 - It may be possible for some maximum terminal assemblies to use two M20/O entry positions.
Rails (PL513, PL520, PL612, PL615, PL620 and PL712) 1 Diagonal rail.
PL511, PL626 and PL722: 1 Horizontal rail.
PL630: 1 diagonal or 2 vertical rails.
中國區(qū)分銷商:
上海頤品自動化科技有限公司
Shanghai Epin Automation Co.,Ltd.
Website:www.epinautomation。。com
:sales@epinautomation.com
*:
請輸入賬號
請輸入密碼
請輸驗證碼
以上信息由企業(yè)自行提供,信息內容的真實性、準確性和合法性由相關企業(yè)負責,儀表網(wǎng)對此不承擔任何保證責任。